# RENDA Nova8 Fits Eight 600W RTX PRO 6000 GPUs in 4U With Self-Contained Liquid Cooling for Air-Cooled Racks

> Source: <https://www.storagereview.com/news/renda-nova8-eight-600w-rtx-pro-6000-gpus-4u-self-contained-liquid-cooling>
> Published: 2026-11-23 17:47:28+00:00

**Recommendation:** When benchmarking dense multi-GPU serving, match replica counts and concurrency before comparing tokens per second and tokens per watt; RENDA's 54,564 tokens-per-second result used one replica per GPU and 512 concurrent requests, not the reference's two replicas and 8,192 users.
More in the playbook "Inference and self-hosting": <https://wpnews.pro/playbooks/inference-serving>

Nexalus and RENDA have built a 4U AI server that runs eight [NVIDIA RTX PRO 6000 Blackwell](https://www.storagereview.com/review/nvidia-rtx-pro-6000-workstation-gpu-review-blackwell-architecture-and-96-gb-for-pro-workflows) GPUs at their full 600W rating inside a standard air-cooled rack. The RENDA Nova8 carries a self-contained liquid loop for every GPU and the CPU, so the companies say an operator can swap it into an existing 19-inch rack without adding facility piping or other cooling infrastructure. Their internal testing puts the server at up to 55,000 tokens per second on Llama 3.3 70B.

## Jet-Impingement Cooling Across the CPU and GPUs

The Nova8 uses Nexalus’ patented jet-impingement cooling on each GPU and on the CPU. Jets of coolant strike the cold plate directly above the hottest areas of each chip, where a conventional plate pushes coolant along channels. RENDA lists single-slot liquid blocks on the GPUs and a jet-impingement block on the CPU, and the companies describe the server as co-developed and jointly patented.

Ten micropumps move coolant through five redundant loops, and 16 fans in push-pull pairs move air across the internal radiator. RENDA says the server keeps running when a single part fails, and quick-disconnect fittings allow parts to be swapped without draining the loop. The companies have not published how much throughput the server holds with a pump or a fan out of service.

Nexalus and RENDA say the GPUs run more than 20°C below their maximum operating temperature, which they present as thermal headroom for sustained operation and model-specific tuning. RENDA also lists optional rear quick-connects that export heat as water at up to 60°C, for reuse or for rejection through a dry cooler. Without that option, the radiator rejects the heat into the room, so the existing air handling still has to absorb the full load of the server.

## Vendor Testing Reports Up to 55,000 Tokens per Second

RENDA tested with Llama 3.3 70B Instruct in NVFP4 on TensorRT-LLM, using one replica per GPU, 512 concurrent requests per replica, and 256 input and 256 output tokens. With all eight GPUs held to a 600W limit, the best tuned run reached 54,564 tokens per second, and a one-hour run averaged 53,984. RENDA says the tuned runs set GPU clock offsets through NVIDIA’s management tools, with no other hardware changes.

The companies claim up to 20% more throughput than comparable air-cooled systems and 8.6 tokens per watt, which they put at up to 22% better efficiency in the same rack footprint. RENDA’s reference is a published result of 45,527 tokens per second and 7.03 tokens per watt from a tier-one air-cooled server with eight RTX PRO 6000 Blackwell Server Edition GPUs, where the Nova8 test used Workstation Edition cards. That reference ran two EPYC CPUs, two replicas per GPU, and 8,192 concurrent users, so the two results come from different serving configurations.

At 8.6 tokens per watt, the best run works out to about 6.3kW of system power, which lines up with the roughly 6.4kW that RENDA estimates for a typical full load. These are vendor results, and we did not run or audit them.

## Deployment Within Existing Air-Cooled Facilities

RENDA pairs the GPUs with a single AMD EPYC processor, up to 2TB of DDR5 RDIMM memory, and eight U.2 PCIe Gen5 NVMe drives. Four 3kW 80 PLUS Titanium power supplies run in a 2+2 redundant arrangement, and the system ships with Linux, NVIDIA drivers, and TensorRT-LLM installed. RENDA also lists compatibility with vLLM, NVIDIA NIM, and other CUDA inference stacks. The company has not named the EPYC model or the network options.

For operators, the appeal is a 4U server that needs rack space, power, and room air, with no facility water loop or coolant distribution unit to install. That still places about 6.4kW of heat per server in a rack planned around air cooling. Three servers in one rack come to roughly 19kW in 12U, which is more than many air-cooled rows are typically provisioned to remove. Nexalus and RENDA have not published inlet temperature limits, airflow requirements, dimensions, or weight.

| **Specification** | **RENDA Nova8** | 
|---|---|
| **Form Factor** | 4U, standard 19-inch rack | 
| **GPUs** | 8 x NVIDIA RTX PRO 6000 Blackwell 96GB GDDR7 with ECC per GPU, 768GB total 600W per GPU | 
| **CPU** | 1 x AMD EPYC (model not disclosed) | 
| **Memory** | Up to 2TB DDR5 RDIMM | 
| **Storage** | 8 x U.2 PCIe Gen5 NVMe | 
| **Power Supplies** | 4 x 3kW 80 PLUS Titanium, 2+2 redundant | 
| **System Power** | About 6.4kW typical at full load (RENDA estimate) | 
| **Cooling** | Nexalus jet-impingement liquid cooling on every GPU and the CPU 10 micropumps in 5 redundant loops 16 fans | 
| **Heat Export** | Optional rear quick-connects Up to 60°C water out | 
| **Software** | Linux with NVIDIA drivers and TensorRT-LLM preinstalled | 
| **Vendor-Tested Throughput** | Up to 55,000 tokens per second 53,984 tokens per second one-hour average Llama 3.3 70B, NVFP4 | 
| **Vendor-Tested Efficiency** | 8.6 tokens per watt | 
| **Availability** | Pre-order Remote Test Drive for qualified organizations | 
| **After-Sales Service** | UNICOM Engineering | 

## Pre-Orders and Remote Testing

Qualified organizations can pre-order the Nova8 or request a remote Test Drive, which gives vetted prospects access to a live server to validate their models before buying. Global after-sales service runs through Nexalus partner UNICOM Engineering. RENDA is operated by Overclockers UK, part of Pro Gamers Group, and Nexalus is a liquid cooling specialist based in Cork, Ireland. Neither company has disclosed pricing or a shipping schedule.

MSI showed a rack-level approach to the same GPU at OCP, with up to 32 RTX PRO 6000 cards across four [liquid-cooled CG681-S6093 MGX servers](https://www.storagereview.com/news/msi-ocp-2026-liquid-cooled-cg681-s6093-mgx-rack-32-rtx-pro-6000).