{"slug": "nobody-has-to-certify-the-psus-powering-ai-data-centers", "title": "Nobody Has to Certify the PSUs Powering AI Data Centers", "summary": "No law anywhere requires an independent lab to verify the efficiency of data center power supplies (PSUs), leaving compliance to manufacturer self-declaration or voluntary labels, according to HWBusters and Cybenetics lab operator Aris Mpitziopoulos. The IEA's Energy and AI report estimates data centers consumed about 415 TWh in 2024, roughly 1.5% of global electricity, rising to about 945 TWh by 2030 and 1,200 TWh by 2035, while Lawrence Berkeley National Laboratory counted 176 TWh in the US in 2023 (4.4% of national electricity) and projects 325 to 580 TWh by 2028. The EU's Regulation (EU) 2019/424 has set minimum server PSU efficiency since 2020 — 90% at 10% load, 94% at 20%, 96% at 50% and 91% at 100% for single-output units — but compliance is self-declared under CE marking, DC-powered servers are excluded, and the European Commission's review, due by March 2022, remains listed as \"under review.", "body_md": "AI has turned data centers into one of the fastest-growing electricity users on the planet. In its [Energy and AI report](https://www.iea.org/reports/energy-and-ai/energy-demand-from-ai), the IEA estimates that data centers used about 415 TWh in 2024, around 1.5% of the world’s electricity. In its Base Case, this becomes about 945 TWh by 2030 and about 1,200 TWh by 2035. In the US, [Lawrence Berkeley National Laboratory](https://eta-publications.lbl.gov/publications/2024-lbnl-data-center-energy-usage-report) counted 176 TWh in 2023, 4.4% of the country’s electricity, and expects 325 to 580 TWh by 2028. That would be 6.7% to 12% of all US electricity.\n\nEvery one of those kilowatt-hours goes through power supplies before it reaches a chip, usually more than one. So here is a question I keep asking: who checks how efficient those power supplies really are? The honest answer is the manufacturer itself, or a voluntary label it chose to apply for. As far as I can find, no law anywhere requires an independent lab to verify the efficiency of a data center PSU. Someone buying an 850 W PSU for a gaming PC has more independent efficiency data to choose from than an operator buying thousands of server modules that run 24/7.\n\nBefore I go further, you should know where I stand. I run HWBusters and the Cybenetics lab, and Cybenetics would gain from what I propose here, because we test and certify power supplies for a living. Keep that in mind and check my sources. Every number below is linked.\n\n## Where the power goes\n\nIn a typical data center, electricity from the grid passes through a transformer, an uninterruptible power supply (UPS), and power distribution units (PDUs). Then the server PSU, or a power shelf that feeds a whole rack, converts it to a low DC voltage, and converters on the board step it down again for the CPU or GPU. Every step loses a little. The server PSU is the one stage that every server has, and it never switches off.\n\nThe diagram shows the uncomfortable part. Transformers have [mandatory EU efficiency rules](https://eur-lex.europa.eu/eli/reg/2019/1783/oj). The UPS has only voluntary programs. The server PSU has a minimum in the EU that the manufacturer declares itself, and nothing mandatory in the US. DC and high-voltage DC (HVDC) supplies, where the industry is heading, have no rules at all.\n\n## What the rules already do\n\nCredit where it is due. The EU has had minimum efficiency rules for server PSUs since 2020, in [Regulation (EU) 2019/424](https://www.legislation.gov.uk/eur/2019/424/annex/II). Since 1 January 2023, a single-output server PSU must reach 90% efficiency at 10% load, 94% at 20%, 96% at 50% and 91% at 100%, with a power factor of at least 0.95 at half load. Multi-output units need 90%, 94% and 91% at 20%, 50% and 100% load. Those are demanding numbers.\n\nThree details matter, though. Compliance is self-declared under CE marking, so no independent lab has to confirm the numbers before a product goes on sale. The PSU limits exclude DC-powered servers. And the regulation exempts several server types, including servers with more than four processor sockets, large servers, fully fault-tolerant servers and network servers. The Commission was supposed to review the regulation by March 2022. More than four and a half years later, its own website still lists it as [“under review”](https://energy-efficient-products.ec.europa.eu/product-list/servers-and-data-storage-products_en).\n\nIn the US, I could not find any federal minimum for server power supplies. [ENERGY STAR](https://www.energystar.gov/products/enterprise_servers) includes PSU efficiency and power factor tables in its Computer Servers v4.0 specification, and it requires independent certification: an [EPA-recognized certification body](https://www.energystar.gov/partner-resources/products-partner-resources/third-party-cert/cbs) accredited to ISO/IEC 17065 by an IAF MLA signatory, using data from an ISO/IEC 17025 lab. That is the right model. The catch is that it is voluntary, and it nearly disappeared. The administration’s FY2026 budget request zeroed the program, and Congress [restored full funding](https://www.npr.org/2026/02/03/nx-s1-5684126/energy-star-trump-climate-change) in a law signed on 23 January 2026, with votes of 397-28 in the House and 82-15 in the Senate. In March 2026, EPA and DOE [signed an agreement](https://www.asme.org/government-relations/policy-impact/congress-considers-future-of-energy-star-as-doe-transition-begins) that makes DOE the lead agency.\n\nThen there is [80 PLUS](https://www.clearesult.com/80plus/), run by CLEAResult. It is voluntary too, but it has categories for 230 V, 277 V, 480 V, and 380 V DC redundant data center PSUs, and a new Ruby level that CLEAResult describes as ultimate efficiency for AI data centers. I found no 800 V DC category. Its test method comes from the EPRI/Ecova Generalized Internal Power Supply Efficiency Test Protocol, which checks a handful of fixed load points.\n\nChina went another way. Its GB 43630-2023 standard sets mandatory efficiency limits and grades for tower and rack servers, and servers now need a [China energy label](https://www.nemko.com/blog/more-products-subject-to-energy-efficiency-labeling-in-china). But it rates the whole server with a benchmark; it does not test the PSU on its own, and it covers general-purpose one- and two-socket machines. Blade, multi-node, full-cabinet and HPC systems are left out.\n\nFacility rules are moving faster. Germany’s [Energy Efficiency Act](https://www.whitecase.com/insight-alert/data-center-requirements-under-new-german-energy-efficiency-act) requires new data centers that start operating from 1 July 2026 to reach a power usage effectiveness (PUE) of 1.2 or better, with limits of 1.5 from July 2027 and 1.3 from July 2030 for existing sites, although an amendment that may relax them is being debated. In the EU, data centers with at least 500 kW of IT power already report their energy performance, and on 21 September 2026 the Commission adopted an [A to G rating and label](https://sustainablefutures.linklaters.com/post/102o5fr/eu-commission-adopts-data-centre-sustainability-rating-scheme) based on PUE, water use and other indicators. The first labels are expected in 2027.\n\n## Three blind spots\n\nThe first is the metric itself. PUE, defined in ISO/IEC 30134-2, divides the total energy of the facility by the energy of the IT equipment. The PSU is part of the IT equipment. So a watt wasted inside a server PSU counts as IT energy, exactly like a watt spent on computing. PUE tells you how efficient the building is. It cannot tell you how much your power supplies waste, and neither can a label based on it.\n\nThe second is how efficiency is measured. The EU rule and 80 PLUS check a few fixed load points. That is fine as a minimum, but redundant PSUs share the load with a partner module, so they can spend long periods at light load, and nothing below 10% load is checked at all. In our [redundant server PSU protocol,](https://www.cybenetics.com/data/Cybenetics%20Redundant%20Server%20PSU%20Test%20Protocol_en.pdf) we apply more than 1,450 load combinations from 2% to 100% of the operating range in a hotbox starting near 30°C to simulate a server intake, and we average them. That shows how a unit behaves across its real range, not only at four points.\n\nThe third is where the hardware is going. NVIDIA, working with Google and Microsoft through the Open Compute Project and with more than 80 companies, is moving AI racks to [800 V DC](https://developer.nvidia.com/blog/nvidia-800-v-hvdc-architecture-will-power-the-next-generation-of-ai-factories/): an 800 V DC power rack for existing facilities in the second half of 2026, then full production with its Kyber rack systems in 2027, with row-level busways of up to 2 MW per row. OCP published a [100 kW HVDC power shelf specification](https://www.opencompute.org/documents/orv3-hvdc-lvdc-100kw-power-shelf-spec-1-0-0-pdf/) in February 2026. These are exactly the products the EU PSU limits exclude, because they are DC-powered. Vendors already quote [over 97.5% peak efficiency](https://www.deltaww.com/en-US/products/orv3-server-power/ORV3-3-kW-PSU) for OCP rack PSUs, but a peak is the best point on the curve, not the average a data center actually pays for.\n\nThe UPS, which every serious data center has, is in a similar position. IEC 62040-3 already defines how to measure its efficiency, yet it is covered only by voluntary programs such as the [EU Code of Conduct on AC UPS](https://publications.jrc.ec.europa.eu/repository/bitstream/JRC124951/european_code_of_conduct_ups_2021_pubsy_final_ca_corrected.pdf) and [ENERGY STAR](https://energystar.gov/sites/default/files/asset/document/Final%20Draft%20Version%202.0%20UPS%20Specification.pdf).\n\n## Why one efficiency point matters\n\nLet me put a number on it, with our own arithmetic. The IEA puts servers at about 60% of electricity use in modern data centers. Apply that to the 945 TWh Base Case for 2030, and about 567 TWh goes into servers. Raise the average PSU efficiency from 95% to 96%, for the same power delivered to the hardware, and the input power drops by 1 − 95/96, about 1.04%. That is about 5.9 TWh a year, before any cooling savings. For scale, [Cyprus used about 5.4 TWh of electricity in 2024](https://www.theglobaleconomy.com/Cyprus/electricity_consumption/). One efficiency point, one Cyprus. This is an order-of-magnitude illustration, not a forecast.\n\nEven at 95%, such a fleet would turn about 28 TWh a year into heat inside the PSUs. And every watt lost in conversion is a watt of heat that the cooling has to remove. The IEA puts cooling at about 7% of electricity in efficient hyperscale sites and over 30% in less efficient enterprise ones, so the real saving is bigger than the PSU loss alone.\n\n## How we could fix it\n\nNone of this needs a new organization. The tools exist: accreditation, standards bodies, procurement rules, and labs. What is missing is someone tying them together. I see four routes, and they work best together.\n\n**1. EU law, now.** The Commission’s [public consultation](https://energy.ec.europa.eu/news/minimum-performance-standards-data-centres-europe-public-consultation-launched-2026-09-21_en) on binding minimum performance standards for data centers is open until 14 December 2026, 23:59 CET, and a legislative proposal is expected in the second quarter of 2027. Its [preparatory study](https://energy.ec.europa.eu/resources/preparatory-studies/minimum-performance-standards-eu-data-centres_en) runs until about early 2028. This is the moment to ask for component-level rules. My wish list: revise Regulation 2019/424 so it covers DC and HVDC supplies and power shelves; measure efficiency across the whole load range at a realistic intake temperature instead of four points; replace self-declaration with certification by ISO/IEC 17065-accredited bodies using ISO/IEC 17025 labs; publish the results in a public database; and let the data center label show whether the installed PSUs and UPS units are certified. UPS units should follow the same path.\n\n**2. A proper IEC test method.** I could not find an IEC standard that rates a server PSU across its load range. The industry still leans on the EPRI/Ecova protocol, which builds on IEEE 1515-2000. IEC already has the pieces around it: IEC 62040-3 for UPS performance and efficiency and IEC 62040-5-3 for DC UPS (both from TC 22/SC 22H), a systems committee for low-voltage DC up to 1,500 V (SyC LVDC), and IEC TS 63236 for 380 V DC data center power. A new work item, proposed through a national committee, could produce a full-range method for AC and HVDC PSUs, and we would offer our protocol as a starting point. Standards take years, but once they exist, regulators can reference them. In Europe, that happens through CENELEC.\n\n**3. Buyers and ENERGY STAR.** Regulation is slow; purchasing is not. Governments and hyperscalers could require independently certified PSUs and UPS units in their tenders tomorrow. ENERGY STAR already has the right structure, and its next server specification could add HVDC supplies and full-range testing. For Cybenetics, the route is to become an EPA-recognized certification body. Our [ISO/IEC 17065 accreditation](https://www.cybenetics.com/accreditation/iso-17065.pdf) comes from the Cyprus Accreditation Body, which signs the European EA MLA, so we would first have to confirm with EPA and DOE how that maps to their IAF MLA requirement.\n\n**4. Partnerships instead of turf wars.** This is where I think progress could be fastest. Our lab is accredited to ISO/IEC 17025 by a body that is an [ILAC MRA signatory](https://ilac.org/signatory-detail/?id=21) for testing, the agreement that lets accredited test reports be accepted across borders. So a certification body such as UL Solutions or TÜV could accept Cybenetics test reports as efficiency evidence in its own certification, without testing the same unit twice. With CLEAResult, the obvious step is to agree on one full-range method for data center PSUs, so a manufacturer runs one test and both programs can use the data. Together we could propose that method to the EU and the IEC, share one public results database, and use witnessed testing in manufacturers’ labs to handle a volume that no single lab can. Cybenetics and 80 PLUS compete, and I will not pretend otherwise. But this problem is bigger than both of us, and buyers need one measurement they can trust, not a logo war.\n\nA certification could also check things that a four-point test never looks at: efficiency at the intake temperatures servers really see, efficiency across the whole input voltage window of an HVDC supply, and the accuracy of the power reading a PSU reports through its PMBus telemetry, which operators can use for their own energy reporting.\n\n## What Cybenetics brings, and what it does not\n\nAs far as I know, Cybenetics is the only organization that runs its own PSU efficiency and noise certification schemes under ISO/IEC 17065 accreditation. Our certificate, C010, was granted by the Cyprus Accreditation Body on 31 August 2026 and covers PSU efficiency (ETA), noise (LAMBDA), and fan performance (PHI). Our [ISO/IEC 17025 accreditation](https://www.cybenetics.com/accreditation/iso-17025.pdf) covers PSU performance and efficiency, noise, conducted emissions, and fan aerodynamics.\n\nWe already run a redundant server PSU program for CRPS and M-CRPS modules, averaged into an [ETA Redundant rating](<https://www.cybenetics.com/index.php?option=eta-(redundant)>) from Bronze to Diamond. Diamond needs at least 95% average efficiency and a power factor of at least 0.95. Today it certifies at 230 V only, and low-line and HVDC inputs are checked only for survival. Our accreditation scope names the desktop PSU protocol, so the server and HVDC programs are the next scope extension. We are ready to extend the program to HVDC and to build programs for data center UPS units.\n\nI also want to be clear about our limits. We are one lab, in Cyprus. We could not certify the world’s data center PSUs alone, and we should not try. That is one more reason to work with others from day one. On the other big part of a data center’s energy bill, cooling, we already certify fans and test CPU coolers, so the methods for airflow and noise exist. Power conversion and cooling both need numbers that someone other than the seller has checked.\n\n## Where I would start\n\n- Answer the EU consultation before 14 December 2026 and ask for independent certification of PSUs, power shelves and UPS units, measured across the load range.\n- Revise Regulation 2019/424 to cover DC and HVDC supplies and to end self-declaration.\n- Start an IEC work item for a full-range PSU efficiency method for AC and HVDC.\n- Ask public and private buyers to require certified efficiency in their tenders.\n- Bring the certifiers and labs, UL, CLEAResult, TÜV, and Cybenetics among them, around one method and one public database.\n- Add realistic intake temperatures and PSU telemetry accuracy to the tests.\n\nThe AI industry measures everything: tokens per second, FLOPS per watt, PUE to two decimals. It should not be hard to also measure, independently, how much power its power supplies waste. If you work in a data center, I would like to hear from you. What efficiency evidence do you get today when you buy PSUs and UPS units, and who measured it?\n\n*The photos in this article are renderings, and the charts and diagrams were made for it. The featured image uses our own lab photo of a CRPS module.*", "url": "https://wpnews.pro/news/nobody-has-to-certify-the-psus-powering-ai-data-centers", "canonical_source": "https://hwbusters.com/freestyle/ai-data-center-psu-efficiency-certification/", "published_at": "2026-11-25 10:45:01+00:00", "updated_at": "2026-11-25 11:15:23.138594+00:00", "lang": "en", "topics": ["ai-infrastructure", "ai-policy"], "entities": ["IEA", "Lawrence Berkeley National Laboratory", "European Commission", "HWBusters", "Cybenetics", "ENERGY STAR", "Regulation (EU) 2019/424"], "also_reported_by": [], "takeaway": null, "recommendation": null, "alternates": {"html": "https://wpnews.pro/news/nobody-has-to-certify-the-psus-powering-ai-data-centers", "markdown": "https://wpnews.pro/news/nobody-has-to-certify-the-psus-powering-ai-data-centers.md", "text": "https://wpnews.pro/news/nobody-has-to-certify-the-psus-powering-ai-data-centers.txt", "jsonld": "https://wpnews.pro/news/nobody-has-to-certify-the-psus-powering-ai-data-centers.jsonld"}}